Isixhobo seVacuum yoQhagamshelwano lokuTshintshela iFuse eDityanisiweyo
Imeko ye-Ambient
1) Ubushushu be-Ambient: -25℃~+45℃, umndilili wemihla ngemihla: ≤35℃
2) Ukuphakama: 1000m(Standard);ingaya kuthi ga kwi-4500m ukulungiselela iodolo ekhethekileyo;
3) Umswakama ohambelanayo: umyinge wemihla ngemihla ≤95%, umyinge wenyanga ≤90%;
4) Ukuqina kwenyikima ≤8 idigri;
I-5) Izihlandlo ezisebenzayo kufuneka zingabikho kwizinto ezinokutsha, iziqhushumbisi, i-corrosives kunye ne-vibration enzima.
IiParameters ezingundoqo zobuGcisa be-Gpvc Vacuum Contactor-fuse Combination Apparatus
Izinto | Iyunithi | Idatha | |||
Ulinganiso lweVoltage | kV | 3.6 | 7.2 | 12 | |
1min Amandla ombane axhathise amandla ombane | kV | 20 | 32 | 42 | |
Impembelelo yokukhanya imelana nombane | kV | 46 | 60 | 75 | |
Ikalwe ngoku | A | 400 | 315 | 200 | |
Ilinganiswe ngexesha elifutshane lokumelana nangoku (4s) | kA | 4 | |||
Incopho elinganisiweyo ukumelana yangoku | kA | 10 | |||
Kulindeleke ukuba kuqhawuke umsinga omfutshane | kA | 50 | |||
Ilindeleke imfutshane-yexesha elikufutshane ngoku | kA | 130 | |||
Uchaso oluphambili lwesekethe | uΩ | ≤250+RFuse | |||
Max.udluliselo lwangoku | A | 4000 | 4000 | 3200 | |
Ilinganiswe ngamaxesha oqhawulo langoku | amaxesha | 250,000 | |||
Ubomi bomatshini | Mechanical ukubamba-uhlobo | amaxesha | 300,000 | ||
Umbane wokubamba-uhlobo | amaxesha | 500,000 | |||
Uchaso oluphambili lwesekethe | uΩ | ≤150 |
Isicwangciso seGpvc Vacuum Contactor-fuse Combination
Inombolo yesicwangciso | Isicwangciso -1 | Isicwangciso - 2 | |
Isicwangciso sokuqala | |||
| Ikalwe ngoku (A) | ~400 | ~400 |
Engundoqo amacandelo | Vacuum contactor-Fuse indibaniselwano - GPVC | 1 | 1 |
I-transformer yangoku i-LZZBJ | 3 | 3 | |
I-voltage transformer JDZ10 okanye i-JDZX10 |
|
| |
I-fuse yombane ophezulu we-XRNM-10 | 3 | 3 | |
Ukutshintshela umhlaba GPJN15-12 |
| 1 | |
Isixhobo sokujonga i-Voltage | Njengeemfuno zabasebenzisi | Njengeemfuno zabasebenzisi | |
Amagqabantshintshi | Ukuqhuba imoto | Ukuqhuba imoto |